.fire product  
       
 

 

Fire Alarm Products

 

 
These products comply with local and international standards & are subjected to continual development / improvement and are subjected to alteration without
notice.
  :::: Detectors
Detectors | Call Points | Sounders, Beacons and Bells | Control Panels
 
 
  Conventional Ioniasation Smoke Detector
Detection Principle Ionization chamber.
Chamber Configuration Twain compensating chambers using one single
sided ionizing radiation source.
Radioactive Isotope Americium 241
Activity 33.3k Becquerels, 0.9 micro-Cuire
Supply Voltage 17 to 28 Volts d.c.
Quiescent Current 30 to 45 micro-Amp at 24 Volts
Normal Alarm Current 61 mA at 28 Volts
52 mA at 24 Volts
18 mA at 10 Volts
Sensitivity Nominal threshold Y value of 0.7 to EN54 Part 7
1984; (BS 5445 Part 7 1984)
Temperature Range Maximum continues operating temperature 60 C
Minimum continues operating temperature 0 C
Minimum operating temperature – 20 C
( no condensation or icing )
 
Humidity 0 % to 95 % relative humidity.
Wind Speed 10 m/s maximum.
     
   
  Conventional Optical Smoke Detector
Detection Principle Photo-electric detection of light scattered in a forward direction by smoke particles.v
Chamber Configuration Horizontal optical bench housing an infra-red emitter and sensor arranged radially to detect forward scattered light
Sensor Silicon PIN photo-diode.
Emitter GaAs Infra-red light emitting diode
Supply Voltage 17 to 28 Volts d.c.
Quiescent Current 30 to 45 micro-Amp at 24 Volts
Normal Alarm Current 61 mA at 28 Volts
52 mA at 24 Volts
18 mA at 10 Volts
Sensitivity Nominal threshold of 3.0 % light grey smoke obscuration per metre to EN 54 Part 7 1984; (BS 5445 Part 7 1984)
Temperature Range - 20 C to +60 C (no condensation or icing).
Humidity 0 % to 95 % relative humidity.(no condensation or icing).
Wind Speed Insensitive to wind.
 
  Conventional Heat Detector
 
Detector Type Rate of rise heat detectors.
Supply Voltage 17 to 28 Volts
Quiescent Current All types: 51 micro-Amp+/-2 micro-Amp, at 24 Volts
Alarm Current 50 – 52 mA at 24 Volts
Storage Temperature Range -30 C to +120 C
Operating Temperature -20 C to + 90 C (no icing).
Humidity 0 % to 95 % relative humidity.


  Optical smoke detector
 
Packing unit 2 pieces per carton
Supply voltage 16 ? 28VDC
Power consumption < 100pA
Operating temperature -10 - +50'C
IP Rating IP 44
Standards EN54-7/9
Dimensions (0 x H) 100 x 44mm (incl. base)
Colour white (uRAL 9010), can be sprayed a
different colour
 
 
  Multisensor smoke detector  
 
Packing unit 2 pieces per carton
Supply voltage 16 - 28VDC
Power consumption < 100pA
Operating temperature -10 - +55'C
IP Rating IP 44
Standards EN54-7
Dimensions (0 x H) 100 x 44mm (incl. base)
Colour white (uRAL 9010), can be sprayed a
different colour
 
  Heat detector (rate of rise and maximum)  
 
Packing unit 2 pieces per carton
Supply voltage 16 - 28VDC
Power consumption < 100pA
Operating temperature -10 - +50'C
IP Rating IP 44
Standards EN54-5 /Al R response class I
prEN54-5 / Al R
(60'C rate of rise and maximum)
Dimensions (0 x H) 100 x 36mm (incl. base)
Colour white (uRAL 9010), can be sprayed a
different colour
     
  Optical smoke detector  
 
Packing unit 2 pieces per carton
Power consumption < 60uA
Operating temperature -25 ~ 60'C
IP Rating IP 44
Standards EN54-7/9
Dimensions (0 x H) 115 x 50 mm (incl. base S0620A)
     
  Remote Iindicator  
 
Supply voltage 16-28V DC
Supervision Current at 28 V DC 0
Maximum Alarm Curren 6 mA
Fire Indicator when Alarm on Mode Red LED on casing
Dimensions 91 mm x 36mm Thickness
Casing ABS Engineering Plastic
Finishing White

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

  :::: Call Points
Detectors | Call Points | Sounders, Beacons and Bells | Control Panels
 
     
  Manual Call Point
Case BS Engineering plastic
Cable Entry Centres for punching or drilling 20mm conduit entries are provided on
to and bottom of the surface fixing box.
Terminals Double terminals for cable to 4mm2
Rating 10 amps at 24V d.c.
3 amps at 48V d.c.
Minimum voltage: 8V a.c. or 8V d.c.
Maximum contact resistance: 0.1. ohm
IP Rating IP 54 with weather resistance gasket.
Note: All other versions are intended for use only in 24V d.c. monitored system
 
  Siemens Manual Call Point

 

 

 

 

Operating voltage 16…26 VDC
Connection terminals 0,2… 1,25mm2
AWG24…15
Operating temperature -25…+70
Humidity _<95% rel
Protection category IP24D
Colour red = RAL3000
Standards prEN54-11
BS5839-2
 

 

 

 

 




 

 

 

 

 

 
:::: Sounders, Beacons and Bells
Detectors | Call Points | Sounders, Beacons and Bells | Control Panels
 
  C & S Youdac Sounder Type Y04
Operating voltage 10 to 35V d.c.
Temperature Operating –25 to +55
Storage –40 to 70
Relative humidity at 40 C 95 %
Protection (BS 5490: 1977) IP54 (improved wether resistance version available).
Terminal capacity 2 x 1.52mm conductors
Approximate nett weight (g) 251
 
C & S Flashalarm Beacon Type V4
Operating voltage 24Vd.c.
Voltage tolerance +25 %
Flash energy (joule) 5 2,5
Light output, opal lens
(candela seconds)
14 4.5
Current consumption (mA) 250 150
Flash rate (Hz) 1
Lens colours Opal, amber, red, green, blue, clear
Temperature range ( C) Operating -25 to +40
Storage -40 to +70
Relative humidity at 40 C 90 %
Protection classification
(BS 5490: 1977)
(Improved wether resistance version available).
Terminal capacity 2 x 1.5 mm conductors
Approximate net weight (g) 240
   
C & S Yodalight Sounder & Flashing Beacon Type YL4
Temperature ( C) Operating -25 to +40
Storage -40 to +70
Relative humidity at 40 C 90 %
Approximately net weight (kg) 0.45
Protection classification IP54 (BS. EN 60529: 1992) (Improved wether resistance version: available).
Operating voltages, d.c 24
Voltage tolerance +20 %
Terminal capacity 2 x 1.5 mm conductors
   
6" Alarm Bell
Model 6” Alarm Bell
Voltage Rating 24V D.C
Alarm Current 0.05 A
Sound Level At 1 meter 95dB
Base Corrosion Resistance
Gong Press Steel
Finish Red
Gong Striker Stainless Steel
   
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

  :::: Control Panels
Detectors | Call Points | Sounders, Beacons and Bells | Control Panels
 
 
Addressable Control Panel
 
Programmable output 8 x 24VDC / 40mA
Relay output 2 x 30VDC / 1A
Transmission output 2 x 30VDC / 1A
Supervised output 4 x 24VDC / 500mA
Programmable input 4
Programmable key input 1
Programmable fire zones 268
Programmable fire control zones 128
Cable specification 150 ohms / 300nF
Mains 115 / 230VAC+10%-15%,50/60Hz
Power consumption < 100VA
Battery 2 x 12V / 15Ah
Standards EN54-2, IEC721-3-3/ 3K5
Colour light grey ( RAL 7035 )
Approvals VdS nr. G298015, LPCB NR. 127c, a.m.m.
     
  Conventional Control Panel

 

 

 

Mains 230V AC +10% / -15%; 50/60 Hz
Power consumption max. 100VA
Emergency power battery 2x12V / 15Ah max
Voltagefree switchover contacts for controls 250VAC / 10A
.Supervised bell 24VDC / 2A
Relay switchover contacts for alarm/fault
30VDC / 1A
Line resistance < 150
Cabinet dimension (WxHxD) 580x480x120mm
Control outputs (drivers) 24VDC / 40mA
Standard EN 54-2, IEC721-3-3/3k5
     
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 